Aerogel Blanket vs Conventional Insulation
For the same steam line, replacing "150 mm aluminum silicate + color steel plate" with "multi-layer 10 mm aerogel + glass cloth + 50 mm aluminum silicate" cut total thickness from 150 mm to 80 mm, reduced surface heat loss from 439 W/m² to 138 W/m² and delivered a 74.6% energy saving rate.
| Item | Conventional scheme | Aerogel scheme |
|---|---|---|
| Total insulation thickness | 150 mm | 80 mm |
| Pipe surface temperature | 40 ℃ | 18 ℃ |
| Surface heat loss | 439 W/m² | 138 W/m² |
| Heat loss along the pipe | 578 W/m | 147 W/m |
| Energy saving rate | — | 74.6% |
| Temperature drop per 1 km | 40 ℃ | 10 ℃ |
Basis: ambient 9 ℃, wind 3 m/s, steam 370 ℃ / 3 MPa, flow 20 t/h (per GB/T 8175-2008).